FC Training Academy · Free engineer tool

Tightness & Purge Calculator

Work out installation volume, the permissible pressure drop and your purge volume for a domestic tightness test to IGEM/UP/1B Edition 4, then save the result as a PDF.

Layout

Job and test context

Premises
Reason for test

Gas and meter

Choose the fuel gas and the meter included in the test. Choose "No meter" when testing from an AECV.

Fuel gas

Pipework

Add each run by material, size and measured length. For hidden runs, use the largest size fitted and round the length up.

Valves and fittings

Use the actual valves and fittings volume where you can work it out; the 10% allowance is the fallback.

Pipework0.00 L
Fittings0.00 L
Meter0.00 L
Installation volume0.000 m³

Training aid based on IGEM/UP/1B Edition 4 (mandatory from 1 October 2026) for domestic installations up to 0.035 m³. It does not replace the standard, manufacturer's instructions or your own judgement. Built by FC Training Academy, Ilford · 0203 883 2009.